The latest version of EZWebCon can be downloaded from the Lantronix website (www.lantronix.com). For
detailed information, refer to the Lantronix documentation.
30.2 LNL-ETHLAN (MSS1/MSS100 Ethernet Controller)
This procedure can also be used for the MSS-VIA network adapter.
This Ethernet controller is a network device, and not a part of the UL certification. This device must have
transient protection.
(A NULL MODEM CABLE IS REQUIRED)
30.2.1 Establish Serial Communication with the ETHLAN
The controller-to-MSS100 or MSS1-T cable is now available, part number HOC-ETHLAN.
UL requirement: this device must be on the recommended UPS (#HO2070) or equivalent
1. With the power OFF to the ETHLAN devices, establish a serial connection from the ETHLAN to the
PC’s Serial Communication Port, for example, using the HyperTerminal. (A Null Modem cable is
required).
2. Start HyperTerminal.
3. Change the Communication settings to 9600 Baud, 8 data bits, 1 stop bit, and Parity None.
4. Plug in power to the ETHLAN. The following messages should appear in the terminal window.
Lantronix Telnet session