Commissioning
Checking Residual Voltage
Input Connections
With Voltage Delivered by 3 VT in
Broken Delta Arrangement
Description
Perform this check when:
b residual voltage is delivered by three VTs on the
secondary circuits connected in a broken delta
arrangement
b the residual current is either calculated in
Sepam™, or it cannot be calculated (for
example,: assembly with two CTs) and is
therefore not available for the protection function.
Block Diagram
Procedure
Use the diagram below to perform the following steps
1 Connect generator voltage terminals to the voltage test terminal box. This will
supply residual voltage input to Sepam™
2 When applicable, connect the generator current terminals to the current test
terminal box, to supply Sepam’s phase 1 current input. This provides a residual
current IrΣ = Ia.
3 Turn the generator on.
4 Apply a V
Ln
voltage set to the rated secondary voltage of the VTs installed in a
broken delta arrangement (depending on the case, V
LL
s / 3 or Uns/3).
DE50712
Note: The number of VTs connected to the Sepam™ voltage connector phase inputs is given as an example and is not used for the test.
* Detection of Plugged Connector (required for proper operation. Installed manually)
5 When applicable, inject an Ia current set to the rated secondary current of the
CTs (1 A or 5 A) and in phase with the voltage applied (specifically, generator
phase displacement α(V
Ln
, I) = 0°).
6 Use the SFT2841 software to check the following:
b the value indicated for measured V0 residual voltage is approximately equal
to the rated primary phase-to-neutral voltage of the VTs (V
Ln
p = V
LLp
/ 3)
b when applicable, the value indicated for the calculated IrΣ residual current is
approximately equal to the rated primary current of the CTs
b when applicable, the value indicated for the phase displacement ϕrΣ (Vr, IrΣ)
between the IrΣ current and Vr voltage is approximately equal to 0°
7 Turn the generator off when the test is completed.
Van
Vbn
Vcn
Vr
Van
Vbn Vcn
Ia = Ir