66
© 2007 Schneider Electric. All Rights Reserved.
1
63230-216-229-B1
Installation
ACE969TP and ACE969FO
Multi-Protocol Interfaces
Connection
Power Supply and Sepam™
b The ACE969 interface connects to C on the Sepam™ base unit (refer to page
13) using a CCA612 cord (length = 3 m or 9.8 ft, green RJ45 fittings)
b 24 to 250 V DC or 110 to 230 V AC operates the ACE969 interface.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
b Only qualified electrical workers should install this equipment. Such
work should be performed only after reading this entire set of
instructions.
b NEVER work alone.
b Before performing visual inspections, tests, or maintenance on this
equipment, disconnect all sources of electric power. Assume that all
circuits are live until they have been completely de-energized, tested,
and tagged. Pay particular attention to the design of the power system.
Consider all sources of power, including the possibility of backfeeding.
b Always use a properly rated voltage sensing device to confirm that all
power is off.
b Screw tight all terminals, even those not in use.
Failure to follow these instructions will result in death or serious injury.
Terminals Type Wiring
DE52166
e1-e2 - supply Screw terminals b Wiring with no fittings:
v One wire with maximum cross-section
0.2 to 2.5 mm²( AWG 24-12) or two
wires with maximum cross-section 0.2 to
1 mm²( AWG 24-18)
v Stripped length: 8 to 10 mm (0.31 to
0.39 in)
b Wiring with fittings:
v recommended wiring with
Telemecanique fitting:
- DZ5CE015D for 1 wire 1.5 mm²
(AWG 16)
- DZ5CE025D for 1 wire 2.5 mm²
(AWG 12)
- AZ5DE010D for 2 wires 1 mm²
(AWG 18)
v Tube length: 0.32 in (8.2 mm)
v Stripped length: 0.31 in (8 mm).
DE51962
Protective ground Screw terminal 1 green/yellow wire, max. length 9.8 ft (3 m)
and max. cross-section 2.5 mm² (AWG 12)
DE51845
Functional ground 0.16 in (4 mm) ring
lug
Grounding braid, supplied for connection to
cubicle grounding