34
© 2007 Schneider Electric. All Rights Reserved.
1
63230-216-229-B1
Installation
LPCT Type Current Sensors
Test Accessories
Accessory Connection Principle
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
b Only qualified electrical workers should install this equipment. Such work
should be performed only after reading this entire set of instructions.
b NEVER work alone.
b Before performing visual inspections, tests, or maintenance on this
equipment, disconnect all sources of electric power. Assume that all
circuits are live until they have been completely de-energized, tested,
and tagged. Pay particular attention to the design of the power system.
Consider all sources of power, including the possibility of backfeeding.
b Always use a properly rated voltage sensing device to confirm that all
power is off.
Failure to follow these instructions will result in death or serious injury.
DE51675
The following describes the connections shown at left:
1 The LPCT sensor is equipped with a shielded cable fitted with a yellow RJ45
radial plug that is plugged directly into the CCA671 connector.
2 Sepam™ protection unit.
3 CCA671 connector, LPCT voltage interface, with microswitch setting of rated
current.
1
4 CCA613 remote test plug, flush-mounted on the front of the cubicle and
equipped with a 3-meter (9.8 ft) cord to be plugged into the test plug of the
CCA670/CCA671 interface connector (9-pin sub-D).
5 ACE917 injection adapter, to test the LPCT protection chain with a standard
injection box.
6 Standard injection box.
Note :
1 Radial plugs for Sepam™ Series 80
Lc
Lb
La
c
b
a
Lc
Lb
La
Lc
Lb
La